Our energy working for you.™
www.cumminspower.com
2011 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product or
service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1591c (6/11)
Control system
PowerCommand control
• The PowerCommand Control is an integrated generator
set control system providing isochronous governing,
voltage regulation, engine protection, generator
protection and operator interface functions.
• Control provides battery monitoring and testing
features, and smart starting control system.
• InPower™ PC-based service tool available for detailed
diagnostics.
• Standard PCCNet RS485 network interface to devices
such as remote annunciator for NFPA110 applications.
• Control boards are potted for environmental protection.
• Suitable for operation in ambient temperatures from
-40 °C to +70 °C (-40 °F to +158 °F), and altitudes to
5000 m (13,000 ft).
• Prototype tested; UL, CSA and CE compliant.
AC protection
• Over current warning and shutdown*
• Over and under voltage shutdown
• Over and under frequency shutdown
• Over excitation
• Field overload
Engine protection
• Overspeed shutdown
• Low oil pressure warning and shutdown*
• High coolant temperature warning and shutdown*
• Low coolant level warning or shutdown*
• Low coolant temperature warning*
• High, low and weak battery voltage warning*
• Fail to start (overcrank) shutdown
• Fail to crank shutdown
• Redundant start disconnect
• Cranking lockout
• Sensor failure indication
• Low fuel pressure warning*
Operator/display panel (optional)
• Manual off switch
• Alpha-numeric display with pushbutton access, for
viewing engine and alternator data and providing setup,
controls and adjustments (English or international
symbols)
• LED lamps indicating genset running, not in auto,
common warning, common shutdown, manual run
mode, remote start
• Suitable for operation in ambient temperatures from
-20 °C to +70 °C (-4 °F to 158 °F).
Alternator data
• Line-to-line and line-to-neutral AC volts*
• Three phase AC current*
• Frequency*
• Total kVA*
*
Optional operator/display panel required to display warnings and
sensor data, and for NFPA 110 and CSA 282 applications.
Engine data
• DC voltage*
• Lube oil pressure*
• Coolant temperature*
Other data
• Genset model data
• Start attempts, starts, running hours
• Fault history
• RS485 Modbus
®
interface
• Data logging and fault simulation (requires InPower
Service Tool)
Digital governing (optional)
• Integrated digital electronic isochronous governor
• Temperature dynamic governing
Digital voltage regulation
• Integrated digital electronic voltage regulator
• Two phase line-to-line sensing
• Configurable torque matching
Control functions
• Time delay start and cooldown
• Cycle cranking
• (2) configurable inputs
• (2) configurable outputs
• Remote emergency stop
Options
¨ Local operator/display panel
¨ Digital electronic governing
¨ Auxiliary output relays (2)
¨ 120/240 V, 100 W anti-condensation heater
¨ Emergency stop switch
¨ Remote annunciator with (3) configurable inputs and (4)
configurable outputs
¨ PowerCommand for Windows remote monitoring
software (direct connect)
¨ Auxiliary, configurable signal inputs (8) and
configurable relay outputs (8)