Natural Gas Generator Set Installation Manual-GF Series
Doc. 17855, Rel. 03/2014
2-2
2.5 Standby Heating Devices
In accordance with NFPA 110, Cummins NPower rec-
ommends installing generator sets (life safety sys-
tems) equipped with engine jacket water coolant
heaters in locations where the minimum ambient tem-
perature is below 4°C (40°F). NFPA also requires that
the engine jacket water coolant be maintained at a
minimum of 32°C (90°F) and, for most applications,
accept the emergency load in 10 seconds or less.
The Engine Cold (Code 1435) message, in conjunc-
tion with illumination of the warning light is provided to
meet the requirements of NFPA 110. The engine cold
sensing logic initiates a warning when the engine
jacket water coolant temperature falls below 21°C
(70°F). In applications where the ambient tempera-
ture falls below 4°C (40°F), a cold engine may be
indicated even though the coolant heaters are con-
nected. Under these conditions, although the genera-
tor set may start, it may not be able to accept load
within 10 seconds. When this condition occurs, check
the coolant heaters for proper operation. If the
coolant heaters are operating properly, other precau-
tions may be necessary to warm the engine before
applying a load.
2.6 Product Modifications
Agency certified products purchased from Cummins
NPower comply only with those specific requirements
and as noted on company product specification
sheets. Subsequent modifications must meet com-
monly accepted engineering practices and/or local,
state and national codes and standards. Product
modifications must be submitted to the local authority
having jurisdiction for approval.
The information, specifications, and recommended
guidelines in this manual are based on information in
effect at the time of printing. Cummnis Npower, LLC.
and Cummins, Inc. reserves the right to make
changes at any time without obligation. If you find dif-
ferences between your engine and the information in
this manual, contact your local Cummins Authorized
Repair Location or call 1-800-DIESEL (1-800-343-
7357) toll free in the U.S. and Canada.
2.7 Product Inquiries (Model 150 GFPA)
For Model 150 GFPA engine related inquires, contact
a PSI representative at the service department
technical support line at 1-888-331-5764 or e-mail
relating to the generator controls on this model,
please contact Npower Service at 1-866-831-7620 or
www.cumminsnpower.com for more information.