Natural Gas Generator Set Installation Manual-GF Series
Doc. 17855, Rel. 03/2014
3-4
WARNING
Battery electrolyte (sulfuric acid) is highly caustic
and can burn clothing and skin. Wear acid imper-
vious neoprene gloves and safety goggles, or full
face shield, when working with the batteries.
Always disconnect the negative (-) battery cable
first and attach the negative (-) battery cable last.
CAUTION
DO NOT connect battery charging cables to any
electronic control system component. This can
damage the electronic control system.
3.3.2 Battery Installation
1. Provide adequate room for servicing or replacing
the batteries. Provide protection from extremes
of temperature and weather.
2. Locate the batteries near the engine or increase
the size of the conductors as required by appli-
cable codes. Ensure that the batteries are con-
figured properly for 24 VDC standard operations.
Refer to Figure 3-1.
3. Check the battery cables and connections to
ensure they are installed correctly and in good
condition.
NOTE: Coat the terminals with NOCO/Anti-OX to
prevent corrosion. Install the cables and tighten the
battery connections.
WARNING
Batteries can emit explosive gases during charg-
ing. Always ventilate the compartment before ser-
vicing the batteries. Remove sources of spark or
open flame. To avoid arcing, remove the negative
(-) battery cable first and attach the negative (-)
battery cable last.
3.4 Exhaust System
WARNING
Inhalation of exhaust gases can result in severe
personal injury or death. Do not use exhaust heat
to warm a room, compartment or storage area.
Pipe exhaust gases to the outside of any enclosure.
Locate the exhaust outlets away from any air inlets to
avoid gases re-entering the enclosure. Exhaust
installations are subject to various detrimental condi-
tions such as extreme heat, infrequent operation and
light loads. Regularly inspect the exhaust system
both visually and audibly to see that the entire system
remains fume tight and safe for operation.
WARNING
Inhalation of exhaust gasses can result in severe
personal injury or death. Use extreme care during
installation to provide a tight exhaust system.
Terminate exhaust pipe away from enclosed or
sheltered areas, windows, doors and vents.
For indoor installation, the exhaust system shall use
sealed joint type fittings, (for example NPT fittings) to
provide a tighter exhaust system. Use of slip type fit-
tings (secured with a muffler clamp) may allow
leakage of exhaust gases into the building.
The exhaust system design should meet Federal,
State and local code requirements.
Use an approved thimble (Figure 3-2) where exhaust
pipes pass through walls or partitions. Insulated wall/
roof thimbles are used where exhaust pipes pass
through a combustible roof or wall. This includes
structures, such as wood framing or insulated steel
decking, etc. Uninsulated wall/roof thimbles are used
where exhaust pipes pass through a non-combustible
wall or roof, such as concrete. Refer to NFPA 37
Stationary Combustion Engines and Gas Turbines”
for accepted design practices. Build according to the
code requirements in effect at the installation site.