CUMMINS ED-3 Manual de instalación Pagina 31

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 67
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 30
Natural Gas Generator Set Installation Manual-GF Series
Doc. 17855, Rel. 03/2014
4-5
prior to shipment. The installer must always check the
stator lead terminal block connections and perform
any necessary reconnect to obtain the voltage
required. Refer to applicable Alternator Installation,
Service & Maintenance Manual as identified in Table
4-4 .
Table 4-4
Some generator sets are capable of producing a wide
range of voltages and connection configurations,
others have specific limited capabilities. Refer to
wiring diagram and generator voltages (from the
nameplate) when reviewing the voltage connection
information and use the wiring diagram supplied with
your generator set when actually performing load
connections.
CAUTION
Reconfiguring generator sets to higher voltages
can exceed the voltage capability of the specific
generator windings. This will damage the genera-
tor, decrease line current, and render line circuit
breakers too large. Consult with your distributor
before performing reconnection for a different
voltage.
CAUTION
Reconfiguring generator sets to lower voltages
can reduce generator set ratings, and also
increase line current, rendering line circuit break-
ers too small. Consult with your distributor before
performing reconnection for a different voltage.
4.6.2 Load Connections
Flexible conduit and stranded conductors must be
used for connections to take up movement of the
generator set.
All loads are connected to the generator by bolting
stranded load wires to the appropriate terminals on
the generator reconnection terminal block or circuit
breaker lugs. The terminals are stamped U, V, W and
N to indicate the line and neutral connections. (Refer-
ence: U, V, and W correspond with L1, L2 and L3;
and N with L0 respectively).
4.6.3 Load Balancing
When connecting loads to the generator set, balance
the loads so the current flow from each line terminal
(L1, L2 and L3) is about the same. This is especially
important if both single phase and three phase loads
are connected. Any combination of single phase and
three phase loading can be used as long as each line
current is about the same, within 10 percent of
median value and no line current exceeds the name-
plate rating of the generator. Check the current flow
from each line after connections by observing the
control panel display.
4.6.4 Current Transformers
The CT’s must be installed as noted in the following
CT Installation Requirements.
Refer to the reconnection diagram to identify the
output leads/phase that must be routed through each
CT, and also appropriate transformer post selection
for meter sensing leads. The transformers are labeled
CT1, CT2 and CT3 on the reconnection wiring dia-
gram. (The reconnection diagram is located on the
upper side cover of the control housing.)
CT Installation Requirements:
The CT has a dot on one side. This dot must be
facing toward the generator (conventional current
flowing into the dot). A dot is also used to indicate pin
1 of the CT.
a. CT1 - U load leads (A phase)
b. CT2 - V load leads (B phase)
c. CT3 - W load leads (C phase)
d. Route the appropriate load wires through
each CT. The CT’s have dual secondaries (3
posts). The CT secondary wire marked 1 is
connected to post 1 of the CT. CT secondary
wire marked 2/3 is connected to post 2 for
high voltage gensets or to post 3 for low
voltage gensets. (Refer to the Reconnection
Diagram in Section 7 - Wiring Diagrams.)
Description Application
Part
Number
Alternator Installation,
Service and Mainte-
nance Manual
UCI, UCM,
UCD 224 &
274
UCH-027
Alternator Installation,
Service and Mainte-
nance Manual
HCI Series UCI-056
Vista de pagina 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 66 67

Comentarios a estos manuales

Sin comentarios