Natural Gas Generator Set Installation Manual-GF Series
Doc. 17855, Rel. 03/2014
3-3
type. The electric valve should be wired so that the
valve is closed when the genset is off.
The recommendations in Cummins Application
Manual T-030 should be followed in regard to fuel
supply system pipe sizes, manual shut-off valves, fuel
filters, and gas pressure regulators.
3.2.3 Fuel Supply Pressure
WARNING
High gas supply pressure can cause gas leaks
which can lead to fire and severe personal injury
or death. Gas supply pressure must be adjusted
to Specifications by qualified personnel.
For propane (vapor withdrawal) and natural gas, the
maximum permissible fuel supply pressure is 5.0 kPa
(20 in WC) and the recommended minimum is 3.7
kPa (15 in WC).
For propane (liquid withdrawal), the maximum per-
missible fuel supply pressure is 2,153 kPa (312 psi)
under any operating condition.
WARNING
Gaseous fuel leaks into an inadequately venti-
lated space can lead to explosive accumulations
of gas. Natural gas rises when released into the
air and can accumulate under overhanging hoods
and inside housings and buildings. Propane
sinks when released into the air and can accumu-
late inside housings, basements and other below-
grade spaces. Precautions must be taken to
prevent gas leaks and the accumulation of
gaseous fuel in the event of a leak.
3.2.4 Check Gas Leaks and Correct
All fuel-system connections, including the container
with associated valves and fittings, must be tested for
leaks with a soap and water solution or equivalent,
while the system is under pressure.
3.2.5 Fuel Heater (Optional-MOH models only)
PECO fuel heaters are available on some MOH
models. They are designed to provide heating of
engine fuel for optimal performance of the Genset.
The PECO Fuel Heater is designed to provide unin-
terrupted fuel flow in cold temperature environments
when it is needed most. Factory Fuel Heater requires
power source to be wired. See owner’s manual for
instructions.
3.2.6 Regulator (Optional)
Prime regulators are available on some models for
fuel pressure reduction from source. Regulators vary
by manufacturer and model. Check with your distribu-
tor or service technician for details on use and set-
tings of your Regulator. Factory Regulator requires
no further installation at site, connect fuel supply.
3.2.7 Fuel Filters (Optional-MOH models only)
Our in-line fuel filters are designed for optimal perfor-
mance of the generator set. They provide the best
choice for Customers who want to extend service
intervals and increase Genset uptime. Optional pres-
sure indicators and automatic drains are available on
some models. Check the installation and service
manuals for your specific filter (models vary by unit)
for details. Factory Fuel Filter require no further
installation at site, connect fuel supply.
3.3 Battery Selection
The minimum recommended reserve capacity (SAE
RC) and cold cranking ampere (SAE CCA) values for
a particular engine can be found on the Model spe-
cific Genset specification sheet is provided with the
genset (visit www.cumminsnpower.com for genset
specifications). RC and CCA definitions can be found
in SAE Standard J537. All battery information is for
lead/acid batteries.
3.3.1 Battery Requirements
For battery replacement information, refer to Figure
3-1. Batteries may be supplied by Cummins Distribu-
tion as an option, or may be supplied by the cus-
tomer.
Figure 3-1 Series Battery Connection - 24 VDC
NG-00045